path: "p/200037/1x6-0mm2-h1z2z2-k-red-dca-500-mtr"
locale: en-gb
alternates:
    nl-nl: "https://www.estg.eu/nl-nl/p/200037/1x6-0mm2-h1z2z2-k-red-dca-500-mtr"
    en-gb: "https://www.estg.eu/en-gb/p/200037/1x6-0mm2-h1z2z2-k-red-dca-500-mtr"
    x-default: "https://www.estg.eu/en-gb/p/200037/1x6-0mm2-h1z2z2-k-red-dca-500-mtr"
    pl-pl: "https://www.estg.eu/pl-pl/p/200037/1x6-0mm2-h1z2z2-k-red-dca-500-mtr"
    de-de: "https://www.estg.eu/de-de/p/200037/1x6-0mm2-h1z2z2-k-red-dca-500-mtr"
    fr-fr: "https://www.estg.eu/fr-fr/p/200037/1x6-0mm2-h1z2z2-k-red-dca-500-mtr"
    it-it: "https://www.estg.eu/it-it/p/200037/1x6-0mm2-h1z2z2-k-red-dca-500-mtr"
    sv-se: "https://www.estg.eu/sv-se/p/200037/athilex-1x6-0mm2-h1z2z2-k-rod-dca-500-m"

title: "Athilex 1x6.0mm2 H1Z2Z2-K Red DCA - 500 Mtr"
description: "Athilex 1x6.0mm2 H1Z2Z2-K Red DCA - 500 Mtr  | One-Stop-Shop | +50 A-brands | Exclusively for Professionals"

type: product_page

---

# Athilex 1x6.0mm2 H1Z2Z2-K Red DCA - 500 Mtr - Art.No.: 200037

## Specifications

- **Brand**: Athilex
- **HS code**: 85444995
- **Manufactor**: Athilex
- **Net Weight**: 20 KILOGRAM
- **Origin**: Italy
- **Cable color**: red
- **Cable type**: Solar
- **Model**: Cable
- **Packaging type**: Roll 500 meter
- **Safety**: DCA

Please note! Cables with a DCA label cannot be used in Belgium.
Nominal Voltage: Uo/U 1.0/1.0 kV AC – 1.5/1.5 kV DC
Maximum Permitted Voltage: 1.8 kV DC
Test Voltage: 6.5 kV AC
Operating Temperature: -40°C up to +90°C
Max. Core Temperature: +120°C (for 20.000 hrs.)
Min. Bending Radius: 5 x cable diameter (fixed installation)
CPR: Dca-s2,d2,a1
Approval: TÜV Rheinland
Standards: EN 50618:2014, IEC 60228, EN 50395, EN 50396, EN 60332-1-2, EN 61034-1/2, EN 50525-1, EN 60216-1/2

## Downloads

- [Datasheet Athilex cables H1Z2Z2 K DCA 2020 ENG](https://cdn.estg.eu/p/6/d/9/d/6d9de9d9b9d2b5e78613002b3ea3caddc2b80788_Datasheet_Athilex_cables_H1Z2Z2_K_DCA_2020_ENG.pdf)